Megavolt fined $120,000 after nitrogen was put into a solar farm transformer without a risk assessment

Megavolt Australia has been fined $120,000 over nitrogen use at a NSW solar farm after pleading guilty to a Category 3 work health and safety offence. Justice Paingakulam found the objective seriousness of the offence fell well above the mid-range, with no risk assessment done for the leak detection task and no safety data sheet…

6 min read
NSW Industrial Court
Share this storyLinkedInWhatsAppTeamsFacebookX

Nine cylinders of nitrogen were put into a 225MVA transformer over about an hour and a half at a solar farm at Wuuluman in New South Wales on 12 July 2023. No risk assessment had been carried out before the gas was used at the site, and the Safe Work Method Statement that all workers had signed onto made no mention of leak detection.

The Industrial Court of New South Wales convicted Megavolt Australia Pty Ltd and imposed a fine of $120,000 on 2 October 2026. Megavolt is also to pay SafeWork NSW’s costs as agreed or assessed, and 50% of the fine is payable to the prosecutor under s 122(2) of the Fines Act 1996 (NSW).

At a glance

  • Parties: SafeWork NSW (prosecutor) and Megavolt Australia Pty Ltd (offender)
  • Citation: SafeWork NSW v Megavolt Australia Pty Ltd [2026] NSWIC 57, Paingakulam J
  • Section: Failure to comply with the primary duty in s 19(1) of the Work Health and Safety Act 2011 (NSW), contrary to s 33
  • Outcome: Conviction and a fine of $120,000, plus the prosecutor’s costs
  • Relevance: Contractors installing and maintaining high voltage transformers, and businesses using inert gases such as nitrogen in enclosed plant

Nine cylinders of nitrogen, and a hatch left open

Megavolt’s business provided transformer installation and maintenance services to medium and high voltage industries. About 90% of its work was done as a subcontractor to Siemens Energy Pty Ltd under a Master Procurement Agreement dated 16 December 2020. Siemens Energy engaged it in February 2023 to install two 225MVA transformers at the Wellington North Solar Farm Project on Goolma Road, Wuuluman.

On 11 July 2023 the first transformer would not hold a vacuum and Megavolt began investigating a possible leak. It did not tell Siemens Energy. The next day the vacuum pump was switched off and nitrogen was fed into the system so that pressure in the tank could be held and moisture kept out while the source of the leak was traced. Nine cylinders were added over 1.5 hours.

A trade assistant who had been subcontracted to Megavolt since May 2023 was working on the transformer that morning. He was later sent to help on the second transformer about 30 metres away, then returned. Another worker heard gas escaping from the inspection hatch and later saw the trade assistant on the turret, on his knees, leaning into the manhole. NSW Fire and Rescue HAZMAT personnel attended at approximately 2:45pm and took an oxygen reading at 3:10pm, which showed 20.1% within the hatch against a normal range of 20.0 to 20.8%. The hatch had not been shut since it was opened.

The charge was a Category 3 offence under s 33 of the WHS Act, arising from a failure to comply with the duty in s 19(1). The risk particularised was “the risk to the health and safety of workers as a result of being exposed to high levels of Nitrogen in a confined space while undertaking work at the site”. The maximum penalty was 5,770 penalty units, or $665,233.

The steps the company accepted it could have taken

By its plea, Megavolt accepted it could have assessed the risks of leak detection and of using and handling nitrogen at the site, written a Safe Work Method Statement covering the leak detection task, given the safety data sheet for nitrogen to workers and to Siemens Energy as the Master Procurement Agreement required, and trained workers in confined space work and atmospheric testing. No information, training or instruction had been given to the trade assistant about confined space work, hazardous atmospheres, or the use and handling of nitrogen.

The prosecutor submitted, and Megavolt accepted, that the breach was objectively serious. Justice Paingakulam found the risk was obvious and ought to have been picked up without difficulty, particularly given the company’s experience with nitrogen, and that the controls available to manage it were not onerous.

“Despite this, the risk involved in the process of detecting leaks was not even assessed.” Justice Paingakulam

Her Honour found that Siemens Energy’s general awareness that Megavolt used nitrogen at other sites did not remove the company’s obligation to identify, assess and control risks at this particular site, noting it had done exactly that for other chemicals, such as methylated spirits. Because leak detection was needed on the vast majority of installation jobs, it was a task that ought to have been covered by the Safe Work Method Statement. The objective seriousness was found to fall well above the mid-range.

Why specific deterrence played no part

Moral culpability was reduced. The court accepted that the offence did not stem from a general lack of work health and safety systems, a disregard for workplace safety, or a casual attitude to safety at the site. Siemens Energy’s technical projects manager had formed a positive impression of how Megavolt worked on site and had no concerns about its safety practices.

There were no aggravating factors under s 21A(2) of the Crimes (Sentencing Procedure) Act 1999 (NSW). Megavolt had no prior convictions and had attracted no adverse attention from SafeWork NSW. Its sole director expressed remorse, and the court accepted the apology made on the company’s behalf as genuine. The prosecutor accepted that specific deterrence had no role to play: the company is small, the offending was an aberration, and Megavolt has ceased to trade.

After the incident the director contacted all of Megavolt’s clients and gave notice that the company would not be available to complete those jobs, turning away contracts valued at around $800,000 in total. The company sold its assets and now has no tangible or cash assets. Its only significant asset at 30 June 2025 was outstanding director’s loans totalling $325,152, and it owes $62,000 to the Australian Taxation Office. The director gave evidence that he did not undertake paid work for more than 12 months after the incident for health reasons and received some workers compensation payments during that period. No application was made for the fine to be reduced on the basis of incapacity to pay.

Megavolt indicated a willingness to plead guilty at the third mention on 15 December 2025, with the plea entered on 20 April 2026 after a protracted negotiation over the facts. A discount of 25% was allowed for the utilitarian value of the plea.

$160,000fine before the plea discount
25%discount for the guilty plea
$120,000fine imposed

Justice Paingakulam set the appropriate fine at $160,000, reduced by 25% to $120,000. Megavolt put four comparative Category 3 decisions before the court, including one in which a company and its director were sentenced after a mobile scaffold was blown from a rooftop onto the glass roof of a neighbouring building. Her Honour held that each had significant distinguishing features and that the fines imposed did not define an acceptable range.

The judgment records that the penalty must provide for general deterrence: “The importance of businesses taking care when using hazardous chemicals cannot be overstated and incidents like this underscore the need for that message to be reinforced.” Two findings shaped the assessment of seriousness: that a task carried out on the vast majority of jobs should have been covered by the Safe Work Method Statement, and that a principal’s general knowledge of the practice did not answer the site-specific duty.

Source: [2026] NSWIC 57

General information only. OnNotice reports developments in Australian industrial relations, human resources and workplace law. This article is for education purposes only and is not intended to form professional advice. Always confirm against the primary source and seek specific advice relating to your circumstances.